The Siemens QRB4A-B036B40B combines normal sensitivity with a 36 cm cable and a fitted soft mounting plug. The detector has a 68 mm black housing and 40 mm stripped, ferruled cable ends.
Product Specification
- Normal sensitivity; black 68 mm detector housing.
- Fixed 36 cm cable with 40 mm stripped ends and ferruled conductors.
- Two-core stranded copper cable, 2 × 0.75 mm².
- Factory-fitted soft mounting plug; flange and clamp are not included.
- Frontal and 90-degree lateral flame viewing.
- IP54 housing protection; electrical connections are excluded.
- Safety class II; operating ambient temperature −20 to +60 °C.
- Maximum rated voltage: 10 V; maximum permissible detector cable length: 3 m.
- Maximum spectral sensitivity: approximately 540 nm.
Control Compatibility
For Siemens LMO, LMV2 and LMV3 oil burner controls in intermittent operation. LME7 and LME8 combinations are available on request. The QRB4 signal is polarity-sensitive: the black lead is positive and the blue lead is negative.
Model Comparison
QRB4A-B070B70B: The B070 version has a 70 cm cable and 70 mm stripped ends; this B036 version has a 36 cm cable and 40 mm stripped ends.