Honeywell C7012E1112 is a dynamic self-check UV flame detector with 1 in. NPT mounting. It uses 6 leadwires, 8 ft (2.4 m).
Product specification
C7012E1112 combines a 1 in. NPT mounting connection with the six-lead dynamic self-check arrangement. It uses the R7847C amplifier configuration in compatible 7800 systems. The 1 in. connection differentiates it from C7012E1104.
Replacement options
For a system upgrade assessment, compare C7061A1053 with the original C7012E1112. The C7061 requires the appropriate R7861A amplifier arrangement; R7847C is not the amplifier for the new detector. Controller compatibility, supply, wiring, mounting and flame-failure response must be reviewed together. This is not an unconditional interchange.
You can request original C7012E1112 stock using this page. For the alternative, open the linked model or specify a replacement review in your enquiry.
Control compatibility
Use the matching R7847C dynamic self-check amplifier with a compatible Honeywell 7800 control. The historical manual also lists R7247C systems. Flame-failure response and permitted wiring follow the complete control/amplifier combination.
The manufacturer places C7012 in its discontinued-product archive. Stock supply is quoted against the full model and nameplate.
Compare mounting, connection and replacement paths in the C7012 series guide.