Honeywell C7012F1052 is a dynamic self-check UV flame detector with 1 in. NPT pipe union mounting. It uses 6 leadwires, 8 ft (2.4 m).
Product specification
C7012F1052 has an explosion-proof two-piece enclosure, a 1 in. NPT pipe union and six 8 ft (2.4 m) leadwires. The manufacturer lists Class I, Groups C and D, and Class II, Groups E, F and G. The viewing window is rated 100 psi (690 kPa); device weight is approximately 14.5 lb (6.6 kg).
Replacement options
C7061F2001 is an explosion-proof option for a system upgrade assessment. Verify the required hazardous-location approvals, R7861A amplifier/control combination, shutter supply, mounting and flame-failure response. The ordinary C7061A housing does not provide equivalent explosion protection. This is a system review candidate, not a one-for-one substitution.
You can request original C7012F1052 stock using this page. For the alternative, open the linked model or specify a replacement review in your enquiry.
Control compatibility
Use the matching R7847C dynamic self-check amplifier with a compatible Honeywell 7800 control. The historical manual also lists R7247C systems. Flame-failure response and permitted wiring follow the complete control/amplifier combination.
The manufacturer places C7012 in its discontinued-product archive. Stock supply is quoted against the full model and nameplate.
Compare mounting, connection and replacement paths in the C7012 series guide.