Honeywell C7012A1145 is a UV flame detector with 3/4 in. NPT mounting. It uses 4 leadwires, 8 ft (2.4 m).
Product specification
C7012A1145 is the 3/4 in. NPT, four-lead version. Its solid-state UV sensing circuit works with the specified rectification-type amplifier arrangement. The A model has no mechanical self-check shutter, unlike C7012E and C7012F.
Replacement options
The historical successor was C7012A1152, which is also discontinued. C7061A1053 is an option for a system upgrade assessment with the appropriate R7861A amplifier. Review the flame-safeguard control, wiring, supply, mounting and flame-failure response. This upgrade assessment is based on technical compatibility requirements, not a manufacturer one-for-one replacement notice.
You can request original C7012A1145 stock using this page. For the alternative, open the linked model or specify a replacement review in your enquiry.
Control compatibility
Use a compatible Honeywell rectification or Ampli-Check arrangement; R7847A/B selections depend on the flame-safeguard control. Flame-failure response and permitted wiring follow the complete control/amplifier combination.
The manufacturer places C7012 in its discontinued-product archive. Stock supply is quoted against the full model and nameplate.
Compare mounting, connection and replacement paths in the C7012 series guide.