Honeywell C7061A1079 is a dynamic self-check UV flame detector with 3/4 in. NPT mounting. It uses internal terminal connections.
Product specification
The historical EMEA catalogue identifies C7061A1079 with a focusing lens, 3/4 in. NPT mounting and no fixed lead cable. It uses terminal connections and a dual 120/230 V shutter configuration. Preserve the optical arrangement and voltage selection when sourcing this legacy version.
Replacement options
The historical Honeywell phase-out table identifies C7061A1020. Check the focusing-lens requirement, mounting arrangement and shutter-terminal selection. C7061A1020 manufacturing status is unconfirmed; this historical cross-reference does not establish current factory availability.
You can request original C7061A1079 stock using this page. For the alternative, open the linked model or specify a replacement review in your enquiry.
Control and installation
Use the matching R7861A amplifier and compatible Honeywell flame-safeguard control. The current C7061 manual also documents SLATE R8001S1051 combinations. Select the complete detector, amplifier and control arrangement for the required flame-failure response; the detector alone does not define a universal response time.
The shutter must be aligned as specified in the installation instructions. Flame sighting and start-up checks must distinguish the supervised flame from ignition sparks and adjacent burners.
Compare mounting, connection and replacement paths in the C7061 series guide.