Honeywell C7061A1061 is a dynamic self-check UV flame detector with 3/4 in. NPT mounting. It uses 8 ft (2.4 m) leadwires.
Product specification
The historical EMEA catalogue identifies C7061A1061 with a focusing lens, 3/4 in. NPT mounting and 2.4 m fixed leads. Its single-voltage shutter configuration is 120 V AC. The focusing lens is a meaningful optical difference from a standard-window replacement.
Replacement options
The historical Honeywell phase-out table points to C7061A1053. C7061A1061 has a focusing lens; the standard quartz window on C7061A1053 does not establish the same optical arrangement. Review flame sighting, lens requirements and the mounting adapter before changing models.
You can request original C7061A1061 stock using this page. For the alternative, open the linked model or specify a replacement review in your enquiry.
Control and installation
Use the matching R7861A amplifier and compatible Honeywell flame-safeguard control. The current C7061 manual also documents SLATE R8001S1051 combinations. Select the complete detector, amplifier and control arrangement for the required flame-failure response; the detector alone does not define a universal response time.
The shutter must be aligned as specified in the installation instructions. Flame sighting and start-up checks must distinguish the supervised flame from ignition sparks and adjacent burners.
Compare mounting, connection and replacement paths in the C7061 series guide.